Hitachi WJ200-001S Instruction Manual page 609

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Ver.3− − − − 100
Register
Function name
No.
Start freq. of active frequency
131Fh
matching
1320h
Software lock mode selection
1321h
(Reserved)
1322h
Motor cable length parameter
1323h
Run/power-on warning time
1324h
Rotation direction restriction
1325h
1326h
Reduced voltage start selection
1327h
Function code display restriction
1328h
Initial display selection
Automatic user parameter
1329h
registration
132Ah
Torque limit selection
Torque limit 1 (fwd-power in
132Bh
4-quadrant mode)
Torque limit 2 (rev/regen. in
132Ch
4-quadrant mode)
Torque limit 3 (rev/power in
132Dh
4-quadrant mode)
Torque limit 4 (fwd/regen. in
132Eh
4-quadrant mode)
132Fh
Torque limit LADSTOP enable
1330h
Reverse Run protection enable
1331h to
(Reserved)
1332h
Dual Rating Selection
1333h
Controlled deceleration on power
1334h
loss
DC bus voltage trigger level of
1335h
ctrl. decel.
Over-voltage threshold of ctrl.
1336h
decel.
1337h
Deceleration time of ctrl. decel.
1338h
1339h
Initial freq. drop of ctrl. decel.
133Ah to
(Reserved)
133Eh
Maximum-limit level of window
133Fh
comparators O
Minimum-limit level of window
1340h
comparators O
Hysteresis width of window
1341h
comparators O
Maximum-limit level of window
1342h
comparators OI
Minimum-limit level of window
1343h
comparators OI
Hysteresis width of window
1344h
comparators OI
Function
R/W
code
0 (frequency at the last shutoff), 1 (maximum
b030
R/W
frequency), 2 (set frequency)
0 (disabling change of data other than "b031" when
SFT is on), 1 (disabling change of data other than
"b031" and frequency settings when SFT is on), 2
b031
R/W
(disabling change of data other than "b031"), 3
(disabling change of data other than "b031" and
frequency settings), 10 (enabling data changes
during operation)
-
-
-
b033
R/W 5 to 20
b034 (high)
R/W
0 to 65535
b034 (low)
R/W
0( Enable for both dir)/ 1 (Enable for forward
b035
R/W
only)/ 2 (Enable for reverse only)
0 (minimum reduced voltage start time) to 255
b036
R/W
(maximum reduced voltage start time)
0 (full display), 1 (function-specific display), 2 (user
b037
R/W
setting), 3 (data comparison display), 4 (basic
display), 5(monitor display)
b038
R/W 001-060
b039
R/W 0 (disabling), 1 (enabling)
00 (quadrant-specific setting), 01 (switching by
b040
R/W
terminal), 02 (analog input)
b041
R/W 0 to 200/255 (no)
b042
R/W 0 to 200/255 (no)
b043
R/W 0 to 200/255 (no)
b044
R/W 0 to 200/255 (no)
b045
R/W 0 (disabling), 1 (enabling)
b046
R/W 0 (disabling), 1 (enabling)
-
-
-
b049
R/W 0(CT mode)/1(VT mode)
0 (disabling), 1 (enabling), 2, (nonstop operation at
momentary power failure (no restoration))
b050
R/W
3, (nonstop operation at momentary power failure
(restoration to be done))
b051
R/W 0 to 10000
b052
R/W 0 to 10000
b053 (high)
R/W
0.01 to 36000
b053 (low)
R/W
b054
R/W 0 to 1000
-
-
-
b060
R/W
0. to 100. (lower limit : b061 + b062 *2) (%)
b061
R/W
0. to 100. (lower limit : b060 - b062*2) (%)
b062
R/W
0. to 10. (lower limit : b061 - b062 / 2) (%)
b063
R/W
0. to 100. (lower limit : b064 + b066 *2) (%)
b064
R/W
0. to 100. (lower limit : b063 - b066 *2) (%)
b065
R/W
0. to 10. (lower limit : b063 - b064 / 2) (%)
Monitoring and setting items
Data resolution
-
-
-
-
1 [10h]
-
-
-
-
-
-
1 [%]
1 [%]
1 [%]
1 [%]
-
-
-
-
-
0.1 [V]
0.1 [V]
0.01 [s]
0.01 [Hz]
-
1 [%]
1 [%]
1 [%]
1 [%]
1 [%]
1 [%]