Pulse Train Input Operation

The WJ200 inverter is capable of accepting pulse train input signals, that are used for
frequency command, process variable (feedback) for PID control, and simple positioning.
The dedicated terminal is called "EA" and "EB". Terminal "EA" is a dedicated terminal,
and the terminal "EB" is an intelligent terminal, that has to be changed by a
parameter setting.
Terminal Name
EA
Pulse train input A
EB
Pulse train input B
(Input terminal 7)
(Set
(1) Frequency Command by pulse train input
When using this mode, you should set
by input-capture, and calculated based on the ratio of designated max. frequency
(under 32kHz). Only an input terminal "EA" will be used in this case.
(2) Using for process variable of PID control
You can use the pulse train input for process variable (feedback) of PID control. In this
case you need to set
(3) Simple positioning by pulse train input
This is to use the pulse train input like an encoder signal. You can select three types of
operation.
RS485
comm.
SN
Relay contact
SP EO
AL2 AL1 AL0
Pulse
RS485
Train
comm.
output
Description


to
)
to . Only "EA" input terminal is to be used.

Logic input
7
6
5
4
3
Jumper wire
EA
H
O
OI
L
Pulse
Analog
Train
input
input
For frequency command, 32kHz max.
Common is [L]
27Vdc max.
For frequency command, 2kHz max.
Common is [PLC]
to . In this case the frequency is detected

2
1
L
PLC
P24
AM CM2
12 11
Logic
Analog
output
output
Ratings
489