Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
Func.
Name
Code
Output [11] function
[EDM assignable]
Output [12] function
Alarm relay function
[EO] terminal selection
(Pulse/PWM output)
[AM] terminal selection
(Analog voltage output
0...10V)
Digital current monitor
reference value
Pulse train input/output
scale conversion
"C" Function
Description
48 programmable functions
available for logic (discrete)
outputs
(see next section)
48 programmable functions available
for logic (discrete) outputs
(see next section)
13 programmable functions:
Output frequency (PWM)
Output current (PWM)
Output torque (PWM)
Output frequency (Pulse
train)
Output voltage (PWM)
Input power (PWM)
Electronic thermal load ratio
(PWM)
LAD frequency (PWM)
Output current (Pulse train)
Heat sink temperature
(PWM)
General output (PWM)
Pulse train input monitor
Option(PWM)
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
normally open [NO]
normally closed [NC]
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in (C047)
Set range is 0.01 to 99.99
Run
Defaults
Mode
Initial data
Units
Edit
00
[RUN]
01
[FA1]
05
[AL]
07
07
[LAD]
Rated current
1.00
389
A