Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
Func.
Name
Code
Output [11] function

[EDM assignable]
Output [12] function

Alarm relay function

[EO] terminal selection

(Pulse/PWM output)
[AM] terminal selection

(Analog voltage output
0...10V)
Digital current monitor

reference value
Pulse train input/output

scale conversion
"C" Function
Description
48 programmable functions
available for logic (discrete)
outputs
(see next section)
48 programmable functions available
for logic (discrete) outputs
(see next section)
13 programmable functions:
Output frequency (PWM)
Output current (PWM)
Output torque (PWM)
Output frequency (Pulse
train)
Output voltage (PWM)
Input power (PWM)
Electronic thermal load ratio
(PWM)
LAD frequency (PWM)
Output current (Pulse train)
Heat sink temperature
(PWM)
General output (PWM)
Pulse train input monitor
Option(PWM)
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
normally open [NO]
normally closed [NC]
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in  (C047)
Set range is 0.01 to 99.99
Run
Defaults
Mode
Initial data
Units
Edit
00
[RUN]
01
[FA1]
05
[AL]
07
07
[LAD]
Rated current
1.00
389
A

Advertisement

Table of Contents