Ver.264
Func.
Code
[AM] terminal selection
(Analog voltage output
0...10V)
Digital current monitor
reference value
Output [11] active state
Output [12] active state
Alarm relay active state
Output mode of low current
detection
Low current detection level
Output mode of overload
warning
Overload warning level
Overload warning level, 2
motor
Frequency arrival setting for
acceleration
Frequency arrival setting for
deceleration
PID deviation level
Frequency arrival setting 2
for acceleration
Frequency arrival setting 2
for deceleration
Pulse train input/output
scale conversion
PID FBV output
high limit
"C" Function
Name
11 programmable functions:
Output frequency
Output current
Output torque
Output voltage
Input power
Electronic thermal load ratio
LAD frequency
Heat sink temperature
Output torque (with code)
General output
Option
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated current
Select logic conversion, two option codes:
normally open [NO]
normally closed [NC]
Two option codes:
During acceleration, deceleration
and constant speed
During constant speed only
Set the level of low load detection, range
is 0.0 to 2.0*inverter rated current
Two option codes:
During accel., decel. and constant
speed
During constant speed only
Sets the overload warning signal level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Sets the overload warning signal level
nd
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Sets the frequency arrival setting
threshold for the output frequency during
acceleration,
range is 0.0 to 400.0 Hz
Sets the frequency arrival setting
threshold for the output frequency during
deceleration,
range is 0.0 to 400.0 Hz
Sets the allowable PID loop error
magnitude (absolute value), SP-PV, range
is 0.0 to 100%
Set range is 0.0 to 400.0 Hz
Set range is 0.0 to 400.0 Hz
If EO terminal is configured as pulse
train input (C027=15), scale conversion is
set in C047.
Pulse-out = Pulse-in (C047)
Set range is 0.01 to 99.99
When the PV exceeds this value, the PID
loop turns OFF the PID second stage
output, range is 0.0 to 100%
Description
Run
Mode
Defaults
Edit
A
B
Initial data
Units
07
[LAD]
Rated
current
00
00
01
01
INV rated
current
01
Rated
current
x 1.15
Rated
current
x 1.15
0.00
Hz
0.00
Hz
3.0
0.00
Hz
0.00
Hz
1.00
100.0
A
A
A
A
%
%