Hitachi WJ200-001S Instruction Manual page 495

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Ver.266
Func.
Code
OI input span calibration

Thermistor input (PTC) span

calibration
Debug mode enable *

Communication selection

EzCOM start adr. of master

EzCOM end adr. of master

EzCOM starting trigger

Up/Down memory mode

selection
Reset selection

Restart mode after reset

UP/DWN clear mode

EO gain adjustment

AM gain adjustment

AM bias adjustment

Overload warning level 2

Output [11] on delay

Output [11] off delay

Output [12] on delay

"C" Function
Name
Scale factor between the external
frequency command on terminals L–OI
(voltage input) and the frequency output,
range is 0.0 to 200%
Scale factor of PTC input.
Range is 0.0 to 200%
Displays debug parameters.
Two option codes:
Disable
Enable <Do not set>
(for factory use)
Modbus-RTU
 EzCOM
 EzCOM<administrator>
1. to 8.
1. to 8.
 Input terminal
 Always
Controls speed setpoint for the inverter
after power cycle.
Two option codes:
Clear last frequency (return
default frequency )
Keep last frequency adjusted by
UP/DWN
Determines response to Reset input [RS].
Four option codes:
Cancel trip state at input signal ON
transition, stops inverter if in Run
Mode
Cancel trip state at signal OFF
transition, stops inverter if in Run
Mode
Cancel trip state at input ON
transition, no effect if in Run Mode
Clear the memories only related to
trip status
Determines the restart mode after reset
is given, three option codes:
Start with 0 Hz
Start with freq. matching
Start with active freq. matching
Freq. set value when UDC signal is given
to the input terminal, two option codes:
0 Hz
Original setting (in the EEPROM
memory at power on)
Set range is 50 to 200%
Set range is 50 to 200%
Set range is 0 to 100%
Sets the overload warning signal level
between 0% and 200% (from 0 to two time
the rated current of the inverter)
Set range is 0.0 to 100.0 seconds.
Set range is 0.0 to 100.0 seconds.
Description
to
Run
Mode
Defaults
Edit
A
B
Initial data
Units
100.0
100.0
00
00
 
1.
 
1.
 
00
 
00
00
00
00
100.
100.
0.
Rated
current
x 1.15
0.0
0.0
0.0
%
%
%
%
%
A
s
s
s