Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run
command via the terminal [RV], the inverter executes the Reverse Run command
(high) or Stop command (low).
Option
Terminal
Code
Symbol
FW
RV
Valid for inputs:
Required settings
Notes:
When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
When a terminal associated with either [FW] or
[RV] function is configured for normally closed,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
NOTE: The parameter , Keypad Run Key Routing, determines whether the single
Run key issues a Run FWD command or Run REV command. However, it has no effect
on the [FW] and [RV] input terminal operation.
WARNING: If the power is turned ON and the Run command is already active, the
motor starts rotation and is dangerous! Before turning power ON, confirm that the Run
command is not active.
Function Name
State
Forward Run/Stop
Reverse Run/Stop
~
=
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
Example (default input configuration shown
– see
page
3-85)
7
6
5
See I/O specs on
Description
RV FW
PLC
4
3
2
1
L
page
4-6.
P24