Modbus Holding Registers
The following tables list the holding registers for the inverter interface to the network. The table legend
is given below.
• Function Code
Function Code - - - - The inverter's reference code for the parameter or function (same as inverter keypad
Function Code
Function Code
display)
• Name
Name
Name - - - - The standard functional name of the parameter or function for the inverter
Name
• R/W
R/W - - - - The read-only(R) or read-write access(R/W) permitted to the data in the inverter
R/W
R/W
• Description
Description - - - - How the parameter or setting works (same as Chapter 3 description).
Description
Description
• Reg.
Reg. - - - - The network
Reg.
Reg.
address.
• Range
Range - - - - The numerical range for the network value that is sent and/or received
Range
Range
TIP:
TIP:
TIP:
TIP: The network values are binary integers. Since these values cannot have an embedded decimal point,
for many parameters it represents the actual value (in engineering units) multiplied by a factor of 10 or
100. Network communications must use the listed range for network data. The inverter automatically
divides received values by the appropriate factor in order to establish the decimal point for internal use.
Likewise, the network host computer must apply the same factor when it needs to work in engineering
units. However, when sending data to the inverter, the network host computer must scale values to the
integer range listed for network communications.
• Resolution
Resolution
Resolution
Resolution - - - - This is the quantity represented by the LSB of the network value, in engineering units.
When the network data range is greater than the inverter's internal data range, this 1-bit resolution
will be fractional.
Register No.
0000h
unused
0001h
Frequency source
0002h
0003h
Inverter status A
0004h
Inverter status B
0005h
Inverter status C
0006h
PID feedback
0007h
to
(Reserved)
0010h
register address offset
Function name
Function code
-
F001 (high)
F001 (low)
-
-
-
-
-
for the value. Some values have a high-byte and low-byte
R/W
Monitoring and setting items
-
Inaccessible
R/W
0 to 40000 (valid when A001 = 03)
R/W
0: Initial status
2: Stopping
R
3: Running
4: Free-run stop
5: Jogging
R
0: Stopping, 1: Running, 2: Tripping
0: ---
1: Stopping
2: Decelerating
R
3: Constant-speed
operation
4: Accelerating
5: Forward rotation
R/W
0 to 10000
R
-
Data
resolution
0.01 [Hz]
6: DC braking
7: Retrying
8: Tripping
9: Undervoltage (UV),
6: Reverse rotation
7: Switching from fwd.
to rev. rotation,
8: Switching from rev.
to fwd. rotation,
9: Starting fwd.
10: Starting rev.
0.01 [%]
-
-
-
-