Hitachi WJ200-001S Instruction Manual page 400

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Fine Tuning Functions
Func.
Name
Code
Restart mode on power
B001
failure / under-voltage trip
Allowable under-voltage
B002
power failure time
Retry wait time before motor
B003
restart
Instantaneous power failure /
B004
under-voltage trip alarm
enable
Number of restarts on power
B005
failure / under-voltage trip
events
Restart frequency threshold
b007
Restart mode on over voltage
b008
/ over current trip
"b" Function
Description
Select inverter restart method,
Five option codes:
00...Alarm output after trip, no
automatic restart
01...Restart at 0Hz
02...Resume operation after
frequency matching
03...Resume previous freq. after
freq. matching, then
decelerate to stop and display
trip info
04
...Resume operation after active
freq. matching
The amount of time a power input
under-voltage can occur without
tripping the power failure alarm.
Range is 0.3 to 25 sec. If
under-voltage exists longer than
this time, the inverter trips, even
if the restart mode is selected.
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
Three option codes:
00...Disable
01...Enable
02...Disable during stop and
decelerates to a stop
Two option codes:
00...Restart 16 times
01...Always restart
Restart the motor from 0Hz if the
frequency becomes less than this
set value during the motor is
coasting, range is 0 to 400Hz
Select inverter restart method,
Five option codes:
00...Alarm output after trip, no
automatic restart
01...Restart at 0Hz
02...Resume operation after
frequency matching
03...Resume previous freq. after
active freq. matching, then
decelerate to stop and display
trip info
04...Resume operation after active
freq. matching
C− − − − 13
Run
Mode
Defaults
Edit
A
B
Initial data Units
00
1.0
sec.
1.0
sec.
00
00
0.00
Hz
00