3120
Speed/positioning switching function (SPD)
- Set SPD terminal ON, then speed control is enabled in simple positioning mode.
- While SPD terminal is ON, current position counter is 0. When SPD is turned OFF,
the inverter starts positioning operation.
- If positioning command data is 0 at SPD turning OFF, the inverter start deceleration
immediately. (Depending on DC braking setting, motor could be hunting.)
- While SPD terminal is ON, rotating direction depends on RUN command. Be sure to
check rotating direction after switching to positioning operation.
Output Frequency
SPD input
Parameter
Start position counting
Speed control
ON
Item
Input [1]~[7] function
Position control
Data
Time
Target position
Description
SPD: Speed/position
change over