Frequency Arrival Signals
Frequency Arrival
The
current velocity profile of the inverter. As the name implies, output [FA1] turns ON
when the output
Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
For example, you can have an output turn ON at one frequency during acceleration,
and have it turn OFF at a different frequency during deceleration. All transitions have
hysteresis to avoid output chatter if the output frequency is near one of the thresholds.
Option
Terminal
Code
Symbol

FA1
Frequency Arrival
Type 1 – Constant
Speed

FA2
Frequency Arrival
Type 2 – Over
frequency

FA3
Frequency Arrival
Type 3 – Set
frequency

FA4
Frequency Arrival
Type 4 – Over
frequency (2)

FA5
Frequency Arrival
Type 5 – Set
frequency (2)
11, 12, AL0 – AL2
Valid for inputs:
, , , ,
Required
settings
Notes:
 For most applications you will need to use only
one type of frequency arrival outputs (see
examples). However, it is possible assign both
output terminals to output functions [FA1] and
[FA2]
 For each frequency arrival threshold, the output
anticipates the threshold (turns ON early) by
1.5Hz
 The output turns OFF as the output frequency
moves away from the threshold, delayed by
0.5Hz
 The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the
coil from damaging the inverter's output
transistor
group of outputs helps coordinate external systems with the
frequency arrives
Function Name
State
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
at the standard set frequency (parameter F001).
when output to motor is at the constant frequency
when output to motor is OFF, or in any acceleration or
deceleration ramp
when output to motor is at or above the set frequency
thresholds for, even if in acceleration or decel ramps
when output to motor is OFF, or during accel or decel
before the respective thresholds are crossed
when output to motor is at the set frequency
when output to motor is OFF, or in any acceleration or
deceleration ramp
when output to motor is at or above the set frequency
thresholds for, even if in acceleration or decel ramps
when output to motor is OFF, or during accel or decel
before the respective thresholds are crossed
when output to motor is at the set frequency
when output to motor is OFF, or in any acceleration or
deceleration ramp
Example for terminal [11] (default output configuration
shown – see page 3-89):
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
Power
supply
See I/O specs on
page 4-6
Description
FA1
11
RY
page 4-51 and
3-91):
FA1
AL1
AL2
Load
455