422
Two Stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings
and
)
acceleration/ deceleration values. When the
terminal is turned OFF, the inverter is
returned to the original acceleration and
deceleration time
and

(acceleration time 2) and
time 2) to set the second stage acceleration
and deceleration times.
In the graph shown above, the [2CH] becomes active during the initial acceleration.
This causes the inverter to switch from using acceleration 1 () to acceleration 2
().
Option
Terminal
Code
Symbol

2CH
Valid for inputs:
Required settings
Notes:
 Function

selects the method for second
stage acceleration. It must be set =
the input terminal method in order for the [2CH]
terminal assignment to operate.
to
use
the
second
(
acceleration time 1,
deceleration time 1). Use

Function Name
Two-stage Accelera-
tion and
Deceleration
~
, ,
=

to select
(
set
of
Output
frequency
[2CH]

[FW,RV]
(deceleration
State
ON
Frequency output uses 2nd-stage acceleration and
deceleration values
OFF
Frequency output uses the initial acceleration 1 and
deceleration 1 values
Example (default input configuration shown—see
page
3-85):
7
6
See I/O specs on
Target
frequency
second
initial
1
0
1
0
Description
2CH
5
4
3
2
1
L
page 4–6.
t
P24
PLC