The inverter control section can be powered externally with 24 Vdc as shown below.
This will allow you to read and write parameters using the keypad or
via communication (such as Modbus/RTU or with optional fieldBus
communication cards).
NOTE: You CANNOT use the ProDriveNext programming software when powering
the inverter in this way! It will also not be possible to drive a motor.
By having ability inverter doesn't block the current flowing into itself when it is not
powered. This may cause the closed circuit when two or more inverters are connected to
common I/O wiring as shown below to result in unexpected turning the on the input. To
avoid this closed circuit, please put the diode (rated:50V/0.1A) in the path as described
below.
P24
PLC
L
1
7
WJ200
P24
PLC
L
1
7
P24
PLC
L
1
7
415