Func.
Name
Code
Torque limit 3 (rev/power)
Torque limit 4 (fwd/regen.)
Torque LAD STOP selection
Reverse run protection
Dual Rating Selection
Controlled deceleration on
power loss
DC bus voltage trigger level
of ctrl. decel.
Over-voltage threshold of
ctrl. decel.
Deceleration time of ctrl.
decel.
Initial freq. drop of ctrl.
decel.
Maximum-limit level of
window comparator (O)
Minimum-limit level of
window comparator (O)
Hysteresis width of window
comparator (O)
Maximum-limit level of
window comparator (OI)
Minimum-limit level of
window comparator (OI)
Hysteresis width of window
comparator (OI)
Operation level at O
disconnection
Operation level at OI
disconnection
Ambient temperature setting
Watt-hour clearance
Watt-hour display gain
Start frequency
Carrier frequency
"b" Function
Description
Torque limit level in reverse powering
quadrant, range is 0 to 200%/no(disabled)
Torque limit level in forward regen.
quadrant, range is 0 to 200%/no(disabled)
Two option codes:
Disable
Enable
Two option codes:
No protection
Reverse rotation is protected
(CT mode) / (VT mode)
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC bus
voltage controlled
Decelerates to a stop with DC bus
voltage controlled, then restart
Setting of DC bus voltage to start
controlled decel. operation. Range is 0.0
to 1000.0
Setting
the
OV-LAD
controlled decel. operation. Range is 0.0
to 1000.0
Range is 0.01 to 3600.0 seconds.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
Set range, {Min.-limit level () +
hysteresis width ()x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level () -
hysteresis width ()x2} % (Maximum
of 0%)
Set range, 0 to {Max.-limit level () -
Min.-limit level ()}/2 % (Maximum of
10%)
Set range, {Min.-limit level ( +
hysteresis width ()x2} to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level () -
hysteresis width ()x2} % (Maximum
of 0%)
Set range, 0 to {Max.-limit level () -
Min.-limit level ()}/2 % (Maximum of
10%)
Set range, 0 to 100%, or "no" (ignore)
Set range, 0 to 100%, or "no" (ignore)
Set range is,
-10~50 C
Two option codes:
OFF
ON (press STR then clear)
Set range is,
1.~1000.
Sets the starting frequency for the
inverter output, range is 0.10 to 9.99 Hz
Sets the PWM carrier (internal switching
frequency), range is 2.0 to 15.0 kHz
Run
Mode
Edit
A
B
stop
level
of
Ver.259
Defaults
Initial data
Units
200
%
200
%
00
00
00
00
220.0/
V
440.0
360.0/
V
720.0
1.00
s
0.00
Hz
100.
%
0.
%
0.
%
100.
%
0.
%
0.
%
no
-
no
-
40
C
00
-
1.
0.50
Hz
10.0
kHz