Add Frequency – The inverter can add or subtract on offset value to the output
frequency setting which is specified by  (will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter . the ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function  selects whether to add or subtract. By
configuring an intelligent input as the [ADD] terminal, your application can selectively
apply the fixed value in  to offset (positively or negatively) the inverter output
frequency in real time.
Keypad potentiometer
Control terminal

Function
ModBus network input
Calculate function output
ADD frequency

Intelligent input
Func.
Code
ADD frequency

ADD direction select


setting
"A" Function
Name
An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
Two options:
Plus (adds  value to
Minus (subtracts 
value from the output
frequency setting)
Frequency source setting
+
Σ
+/-
[ADD]
Description
the output frequency
setting)
Output frequency setting

ADD direction select
Run
Defaults
Mode
Initial data
Edit
0.00
00
Units
Hz