Option
Terminal
Code
Symbol
FBV
Feedback Value
Check
11, 12, AL0 – AL2
Valid for inputs:
Required settings
, ,
Notes:
The [FBV] is designed for implementing two-stage
control. The PV high limit and PV low limit
and , do not function as
parameters,
process alarm thresholds. Terminal [FBV] does
not provide a PID alarm function.
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name
State
ON
OFF
Description
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit ()
Transitions to OFF when the PID Feedback Value
(PV) exceeds the PID High Limit ()
Transitions to OFF when the inverter goes from
Run Mode to Stop Mode
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
Power
supply
See I/O specs on
page 4-6
473
page
3-89):
FBV
11
RY
page 4-51 and
3-91):
FBV
AL1
AL2
Load