sink/source logic of intelligent input terminals
Sink or source logic is switched by a jumper wire as below.
Wire size for control and relay terminals
Use wires within the specifications listed below. For safe wiring and reliability, it is
recommended to use ferrules, but if solid or stranded wire is used, stripping length should be
8mm.
Relay output terminal
Control logic
terminal
Relay terminal
Sink logic
2
1
L
PLC P24
Jumper wire
Solid
2
mm
(AWG)
0.2 to 1.5
(AWG 24 to 16)
0.2 to 1.5
(AWG 24 to 16)
Source logic
2
1
Jumper wire
Control logic terminal
Stranded
2
mm
(AWG)
0.2 to 1.0
(AWG 24 to 17)
0.2 to 1.0
(AWG 24 to 17)
L
PLC P24
8mm
Ferrule
2
mm
(AWG)
0.25 to 0.75
(AWG 24 to 18)
0.25 to 0.75
(AWG 24 to 18)