Hitachi WJ200-001S Instruction Manual page 566

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Case 2: When selecting 32-bit parameter for an internal register. (Please refer to the page 1 for setting
range.
Reading Holding Register [03h] , Target register = external register
Query:
No
1
Slave address
2
Function code
3
Register start address (high order)
4
Register start address (low order)
5
Number of holding registers (high order)
6
Number of holding registers (low order)
7
CRC-16 (high order)
8
CRC-16 (low order)
Response:
No
Field Name
1
Slave address
2
Function code
3
Exception code
4
CRC-16 (high order)
5
CRC-16 (low order)
Only 16-bit Holding register can be designated as an internal register. So You will get an exception
response if you choose 32-bit register for an internal register.
Field Name
Example
(Hex)
01
83
31
80
E4
Example
(Hex)
01
03
60
Register address value = Register
01
Number - 1
00
One register
01
CB
CA
Ver.3− − − − 57