B4
Inverter Parameter Setup - The inverter has several settings related to Modbus
communications. The table below lists them together. The
which parameters
refer to the host computer documentation in order to match some of its settings.
Func.
Code
A001
Frequency source
A002
Run command source
C071
Communication speed
C072
Modbus Address
C074
Communication parity
C075
Communication stop bit
C076
Communication error select
C077
Communication error time-out
C078
Communication wait time
NOTE: When you change any of the parameters above, the inverter power must be
rebooted in order to activate new parameters. Instead of rebooting, turning ON/OFF of
reset terminal works as same.
must
be set properly to allow communications. You may need to
Name
Required
Required
00Keypad potentiometer
01Control terminal
02Function F001 setting
03Modbus network input
10 Calculate function output
01Control terminal
02Run key on keypad, or digital operator
03 Modbus network input
03 2400 bps
044800 bps
05 9600 bps
06 19.2k bps
0738.4k bps
0857.6k bps
0976.8k bps
10 115.2k bps
Network address, range is 1 to 247
00No parity
01Even parity
02Odd parity
Range is 1 or 2
00Trip (Error code E60)
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerate to a stop
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
column indicates
Settings