Set Second Motor, Special Set
If you assign the [SET] function to an intelligent input terminal, you can select
between two sets of motor parameters. The second parameters store an alternate set of
motor characteristics. When the terminal [SET] is turned ON, the inverter will use the
second set of parameters to generate the frequency output to the motor. When
changing the state of the [SET] input terminal, the change will not take effect until the
inverter is stopped.
When you turn ON the [SET] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the
original settings (first set of motor parameters). Refer to
4–85
for details.
Parameters
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Option
Terminal
Code
Symbol
SET
Set (select) 2nd
Motor data
~
Valid for inputs:
(none)
Required settings
Notes:
If the terminal state is changed while the inverter
is running, the inverter continues using the current
set of parameters until the inverter is stopped.
SET
Parameters
Stop
Run
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
/
-
~/
-
~
-
~/
-
~
Function Name
State
ON
OFF
"2nd Motor Selection" on page
SET
Stop
Run
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Description
causes the inverter to use the 2nd set of motor
parameters for generating the frequency output to
motor
causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Example (requires input configuration—see
page
3-85):
7
6
5
4
See I/O specs on
page 4–6.
421
SET
3
2
1
L
PLC
P24