Func.
Name
Code
Cooling fan control
Clear elapsed time of
cooling fan
Initialization target data
Dynamic braking control
(BRD) selection
BRD activation level
Initialization trigger
(*)
(*) Note: When 01 is set on b180, and SET key is pressed, initialization starts
immediately and there is not any way to restore the previous parameter setting. WJ200
doesn't have a method to trigger the initialization by key action as the other Hitachi
inverter models have.
"b" Function
Description
Selects when the fan is ON during
inverter operation, three options:
Fan is always ON
Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
Fan is temperature controlled
Two option codes:
Count
Clear
Select initialized parameters, four
option codes:
All parameters
All parameters except
in/output terminals and
communication.
Only registered parameters in
xxx.
All parameters except
registered parameters in xxx
and .
Three option codes:
Disable
Enable during run only
Enable always
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
This is to perform initialization by
parameter input with ,
and . Two option codes:
Initialization disable
Perform initialization
371
Defaults
Run
Mode
Initial data
Units
Edit
01
00
00
00
360/
V
720
00