338
Accel/Decel
Standard acceleration and deceleration is
linear. The inverter CPU can also
calculate an S-curve acceleration or
deceleration curve as shown. This profile
is
useful
characteristics in particular applications.
Curve settings for acceleration and
deceleration are independently selected.
To enable the S-curve, use function
(acceleration) and (deceleration).
Func.
Code
Acceleration curve selection
Deceleration curve selection
Acceleration curve constant
Deceleration curve constant
Curvature of EL-S-curve at
the start of acceleration
Curvature of EL-S-curve at
the end of acceleration
Curvature of EL-S-curve at
the start of deceleration
Curvature of EL-S-curve at
the end of deceleration
See next page for the details.
for
favoring
the
"A" Function
Name
Set the characteristic curve of
Acc1 and Acc2, five options:
linear
S-curve
U-curve
Inverse U-curve
EL S-curve
Set the characteristic curve of
Dec1 and Dec2, options are
same as above ()
Range is 01 to 10.
Range is 01 to 10.
Range is 0 to 50%
Range is 0 to 50%
Range is 0 to 50%
Range is 0 to 50%
Output
frequency
Accel. curve selection
Target
freq.
S-curve
load
0
Acceleration period
Description
=
Linear
=
Defaults
Run
Mode
Initial data
Edit
01
01
02
02
10.
10.
10.
10.
t
Units
%
%
%
%