Hitachi WJ200-001S Instruction Manual page 406

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Name
Code
Stop mode selection
B091
Cooling fan control
B092
Clear elapsed time of cooling
B093
fan
Initialization target data
b094
Dynamic braking control
b095
(BRD) selection
BRD activation level
b096
BRD register
b097
Free V/F setting, freq.1
B100
Free V/F setting, voltage.1
b101
Free V/F setting, freq.2
b102
Free V/F setting, voltage.2
b103
Free V/F setting, freq.3
b104
Free V/F setting, voltage.3
b105
"b" Function
Description
Select how the inverter stops the
motor, two option codes:
00...DEC (decelerate to stop)
01...FRS (free-run to stop)
Selects when the fan is ON during
inverter operation, three options:
00...Fan is always ON
01...Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02...Fan is temperature controlled
Two option codes:
00...Count
01...Clear
Select initialized parameters, four
option codes:
00...All parameters
01...All parameters except
in/output terminals and
communication.
02...Only registered parameters in
Uxxx.
03...All parameters except
registered parameters in Uxxx
and b037.
Three option codes:
00...Disable
01...Enable during run only
02...Enable always
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
Set the value of the register
connected to the inverter.By this
setting, b090's upper limit as the
inverter hardware is calcurated
automatically.So, you can focus the
usage ratio as the connected
register.
Range is minimum connectable
register Rbmin to 600.0[ ]
Set range, 0 ~ value of b102
Set range, 0 ~ 800V
Set range, value of b100 ~b104
Set range, 0 ~ 800V
Set range, value of b102 ~b106
Set range, 0 ~ 800V
C− − − − 19
Run
Mode
Defaults
Edit
A
B
Initial data Units
00
01
-
00
-
00
-
00
-
360/
V
720
Min.
Resista
nce
0.
Hz
0.0
V
0.
Hz
0.0
V
0.
Hz
0.0
V