Active Frequency Matching Restart
Goal of the active frequency matching is the same as normal frequency matching.
Difference is the method. Please select the suitable one for your application.
Func.
Name
Code
Current level of active freq.
matching
Deceleration rate of active
freq. matching
Start freq. of active freq.
matching
"b" Function
Description
Sets the current level of active freq.
matching restart, range is
0.1*inverter rated current to
2.0*inverter rated current,
resolution 0.1
Sets the deceleration rate when
active freq. matching restart, range
is 0.1 to 3000.0, resolution 0.1
Three option codes:
freq at previous shutoff
start from max. Hz
start from set frequency
347
Run
Defaults
Mode
Initial data
Units
Edit
Rated
A
current
0.5
sec.
00