Installation

According to the safety standard listed above, please install referring to the example.
Please be sure to use the both GS1 and GS2, and construct the system that GS1
andGS2 are both turned off when safety input is given to the inverter. Be sure to carry
out the proof test when installation is ready before operation.
When the Gate Suppress function is utilized, connect the drive to a safety certified
interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1
and GS2. Follow the wiring instructions in the Instruction manual.
Safety
Safety
I n put
I n put

Components to be combined

Followings are the example of the safety devices to be combined.
Series
GS9A
G9SX
NE1A
In combination with the safety device complying with the class complying PL=d,
PL=d of the inverter is to be achieved.
Manual
Reset
T31 T33
EDM
( Feedback)
input
G9SX - AD
G9SX - AD
PWR
PWR
FB
FB
T1
T1
T2
T2
EI
EI
ED
ED
ERR
ERR
Safety
Unit
Safety
Output
(certificated
acc. to EN954 - 1
S14
S24
and ISO13849 - 1)
Model
Norms to comply
301
ISO13849-2 cat4, SIL3
GS226-T15-RC
IEC61508 SIL1-3
SCPU01-V1
IEC61508 SIL3
CM2
EDM
GS1
GS2
Safety Related Part
KM1
Inverter
with
Safety stop
function
M
reference certificate
06.06.2007
04.11.2004
27.09.2006
E3