Hitachi WJ200-001S Instruction Manual page 206

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Homing function
-
Two different homing functions are available by setting homing mode selection ().
-
When trigger signal of homing (: ORG), the inverter starts homing operation. When
homing is completed, current position data is reset (0).
-
Direction of homing is specified in .
-
If homing is not operated, position at power up is regarded as home position (0).
Code
Homing mode selection

Homing direction

Low speed homing freq.

High speed homing freq.

Input [1]~[7] function
~
(1) Low speed homing (P068 = 00)
ORG input
ORL input
Output Freq.
[1]
(2) High speed homing (P068 = 01)
ORG input
O
ORL input
R
G
Output Freq.
[1]
Item
Data or data range
ON
ON
[2]
Low speed (P070)
[3]
Home position
ON
ON
[2]
High speed (P071)
[3]
Home position
[5]
Low speed (P070)
[4]
Low speed mode

High speed mode

Forward rotation side

Reverse rotation side

0 to 10Hz
0 to 400Hz
ORL: Limit signal of homing

ORG: Trigger signal of homng

[1] Acceleration up to the speed P070.
[2] Running at low speed P070
[3] DC braking when ORL signal ON
Position
[1] Acceleration up to the speed P071.
[2] Running at high speed P071
[3] Deceleration when ORL signal ON
[4] Running at low speed P070 in
reverse
direction
[5] DC braking when ORL signal OFF
Position
3121
Description

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents