Func.
Name
Code
PID FBV output
low limit
Over-torque/under-torque
selection
Over/under-torque level
(Forward powering mode)
Over/under-torque level
(Reverse regen. mode)
Over/under-torque level
(Reverse powering mode)
Over/under-torque level
(Forward regen. mode)
Signal output mode of
Over/under-torque
Electronic thermal warning
level
Zero speed detection level
Heat sink overheat warning
Communication speed
Modbus address
Communication parity
Communication stop bit
Communication error select
Communication error
time-out
Communication wait time
O input span calibration
"C" Function
Description
When the PV goes below this value, the
PID loop turns ON the PID second stage
output, range is 0.0 to 100%
Two option codes:
Over-torque
Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
During accel, decel and constant
speed
During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 C
Eight option codes:
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
76,800 bps
115,200 bps
Set the address of the inverter on the
network. Range is 1 to 247
Three option codes:
No parity
Even parity
Odd parity
Two option codes:
1 bit
2 bit
Selects inverter response to
communications error.
Five options:
Trip
Decelerate to a stop and trip
Disable
Free run stop (coasting)
Decelerates to a stop
Sets the communications watchdog timer
period.
Range is 0.00 to 99.99 seconds.
0.0 = disabled
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. m seconds.
Scale factor between the external
frequency command on terminals L–O
(voltage input) and the frequency output,
range is 0.0 to 200%
Ver.265
Run
Mode
Defaults
Edit
A
B
Initial data
Units
0.0
00
100.
100.
100.
100.
01
90
0.00
Hz
100.
C
05
bps
1.
00
1
bit
02
0.00
0.
ms
100.0
%
%
%
%
%
%
s
%