Hitachi WJ200-001S Instruction Manual page 489

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Ver.260
Func.
Code
Initialization mode

(parameters or trip history)
Country for initialization

Frequency scaling conversion

factor
STOP key enable

Restart mode after FRS

Automatic carrier frequency

reduction
Dynamic braking usage ratio


Stop mode selection

Cooling fan control Note 2)
Clear elapsed time of

cooling fan Note 2)

Initialization target data
Dynamic braking control

(BRD) selection
"b" Function
Name
Select initialized data, five option codes:
Initialization disabled
Clears Trip history
Initializes all Parameters
Clears Trip history and initializes all
parameters
Clears Trip history and initializes all
parameters and EzSQ program
Select default parameter values for
country on initialization, two option
codes:
area A
Specify a constant to scale the displayed
frequency for  monitor, range is 0.01
to 99.99
Select whether the STOP key on the
keypad is enabled, three option codes:
Enabled
Disabled always
 Disabled for stop
Selects how the inverter resumes
operation when free-run stop (FRS) is
cancelled, three options:
Restart from 0Hz
Restart from frequency detected
from real speed of motor (freq.
matching)
Restart from frequency detected
from real speed of motor (active freq.
matching)
Three option codes:
Disabled
Enabled, depending on the output
current
Enabled, depending on the heat-sink
temperature
Selects the rate of use (in %) of the
regenerative braking resistor per 100 sec.
intervals, range is 0.0 to the value
calcurated by the inverter with b097.
If the connected register's allowable
range is narrow than above range,
the register's range is prior.
0%: Function disabled
>0%: Enabled, per value
00 (DEC (decelerate to stop)) / 01 (FRS
(free-run to stop))
00 (Fan is always ON) / 01 (Fan is ON
during run, OFF during stop (5 minute
delay from ON to OFF)) /
02 (Fan is temperature controlled)
00 (Count) / 01 (Clear)
00 (All parameters)/ 01 (All parameters
except
communication.)/ 02 (Only registered
parameters in xxx.)/ 03 (All parameters
except registered parameters in Uxxx
and b037.)
Three option codes:
Disable
Enable during run only
Enable always
Description
area B
in/output
terminals
and
Run
Mode
Defaults
Edit
A
B
Initial data
Units
00
 
01
 
1.00
00
00
01
 
0.0
00
01
 
00
 
00
00
%