Hitachi WJ200-001S Instruction Manual page 392

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Name
Code
[O] input active range end
A014
voltage
[O] input start frequency
A015
enable
Analog input filter
A016
EzSQ function select
A017
Multi-speed operation
a019
selection
Multi-speed freq. 0
A020
Multi-speed freq. 0,
A220
2
motor
nd
Multi-speed freq. 1 to 15
A021
(for both motors)
to
A035
Jog frequency
A038
Jog stop mode
A039
"A" Function
Description
The ending point (offset) for the
active analog input range,
range is 0. to 100.
Two options; select codes:
00...Use offset (A011 value)
01...Use 0Hz
Range n = 1 to 31,
1 to 30 : ×2ms filter
31: 500ms fixed filter with ±
0.1kHz hys.
Select codes:
00...Disable
01...Activate by RPG terminal
02...Activate always
Select codes:
00...Binary operation (16 speeds
selectable with 4 terminals)
01...Bit operation (8 speeds
selectable with 7
terminals)
Defines the first speed of a
multi-speed profile, range is 0.0
/ start frequency to 400Hz
A020 = Speed 0 (1st motor)
Defines the first speed of a
multi-speed profile or a 2nd
motor, range is 0.0 / start
frequency to 400Hz
A220 = Speed 0 (2nd motor)
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021=Speed 1 ~ A035=Speed15
A021 ~ A035
Defines limited speed for jog,
range is from start frequency to
9.99 Hz
Define how end of jog stops the
motor; six options:
00...Free-run stop (invalid
during run)
01...Controlled deceleration
(invalid during run)
02...DC braking to stop(invalid
during run)
03...Free-run stop (valid during
run)
04...Controlled deceleration
(valid during run)
05...DC braking to stop(valid
during run)
Run
Mode
Defaults
Edit
A
B
Initial data
Units
100.
%
01
8.
Spl.
00
-
00
-
6.00
Hz
6.00
Hz
See next
Hz
row
0.0
Hz
6.00
Hz
04
C− − − − 5