Ver.262
Func.
Code
Decel. overvolt. suppress
const.
Decel. overvolt. suppress
proportional gain
Decel. overvolt. suppress
integral time
GS input mode
Display ex.operator
connected
1st parameter of Dual
Monitor
2nd parameter of Dual
Monitor
Frequency set in monitoring
Automatic return to the
initial display
Ex. operator com. loss action
Data Read/Write select
Inverter mode selection
Initialization trigger
(*)
Password Settings A
Password authentication A
Password Settings B
Password authentication B
"b" Function
Name
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 seconds.
Proportional gain when b130=01. Range
is: 0.00 to 5.00
Integration time when b130=01. Range
is: 0.00 to 150.0 seconds.
Two option codes:
No trip (Hardware shutoff only)
Trip
When an external operator is connected
via RS-422 port, the built-in display is
locked and shows only one "d" parameter
configured in:
~
Set any two "d" parameters in b160 and
b161, then they can be monitored in d050.
The two parameters are switched by
up/down keys.
Set range: ~
Two option codes:
Freq. set disabled
Freq. set enabled
10 min. after the last key operation,
display returns to the initial parameter
set by . Two option codes:
Disable
Enable
Five option codes:
Trip
Trip after deceleration to a stop
Ignore
Coasting (FRS)
Decelerates to a stop
Read/Write OK
Protected
Three option codes:
No function
Std. IM (Induction Motor)
PM(Permanent Magnet Motor)
This is to perform initialization by
parameter input with , and
. Two option codes:
Initialization disable
Perform initialization
0000(Invalid Password)
0001-FFFF(Password)
0000-FFFF
0000(Invalid Password)
0001-FFFF(Password)
0000-FFFF
Description
Run
Mode
Defaults
Edit
A
B
Initial data
Units
1.00
0.20
1.0
00
001
001
002
00
00
02
00
00
00
0000
0000
0000
0000
s
s