Hitachi WJ200-001S Instruction Manual page 497

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Ver.268

RV

CF1 *1

CF2

CF3

CF4

JG

DB

SET

2CH
FRS


EXT

USP

CS

SFT

AT
RS


PTC
Option
Terminal
Code
Symbol

STA

STP

F/R
OFF
ON
Reverse Run/Stop
OFF
Multi-speed Select,
ON
Bit 0 (LSB)
OFF
Multi-speed Select,
ON
Bit 1
OFF
Multi-speed Select,
ON
Bit 2
OFF
ON
Multi-speed Select,
Bit 3 (MSB)
OFF
ON
Jogging
OFF
ON
External DC braking
OFF
ON
Set (select) 2nd Motor
Data
OFF
ON
2-stage Acceleration
and Deceleration
OFF
ON
Free-run Stop
OFF
ON
External Trip
OFF
ON
Unattended Start
Protection
OFF
Commercial
power
ON
source switchover
OFF
ON
Software Lock
OFF
Analog Input
ON
Voltage/Current Select
OFF
ON
Reset Inverter
OFF
ANLG
PTC
thermistor
Thermal Protection
(C005 only)
OPEN
Input Function Summary Table
Function Name
Start
ON
(3-wire interface)
OFF
Stop
ON
(3-wire interface)
OFF
FWD, REV
ON
(3-wire interface)
Inverter is in Stop Mode, motor stops
Inverter is in Run Mode, motor runs reverse
Inverter is in Stop Mode, motor stops
Binary encoded speed select, Bit 0, logical 1
Binary encoded speed select, Bit 0, logical 0
Binary encoded speed select, Bit 1, logical 1
Binary encoded speed select, Bit 1, logical 0
Binary encoded speed select, Bit 2, logical 1
Binary encoded speed select, Bit 2, logical 0
Binary encoded speed select, Bit 3, logical 1
Binary encoded speed select, Bit 3, logical 0
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
Inverter is in Stop Mode
DC braking will be applied during deceleration
DC braking will not be applied
The inverter uses 2nd motor parameters for generating
frequency output to motor
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
Frequency
output
uses
deceleration values
Frequency
output
uses
deceleration values
Causes output to turn OFF, allowing motor to free run
(coast) to stop
Output operates normally, so controlled deceleration stop
motor
When assigned input transitions OFF to ON, inverter
latches trip event and displays
No trip event for ON to OFF, any recorded trip events
remain in history until reset
On power up, the inverter will not resume a Run command
(mostly used in the US)
On power up, the inverter will resume a Run command that
was active before power loss
Motor can be driven by commercial power
Motor is driven via the inverter
The keypad and remote programming devices are prevented
from changing parameters
The parameters may be edited and stored
Refer to "Analog Input Settings" on page 3-13.
The trip condition is reset, the motor output is turned OFF,
and power up reset is asserted
Normal power-ON operation
When a thermistor is connected to terminal [5] and [L], the
inverter checks for over-temperature and will cause trip
event and turn OFF output to motor
A disconnect of the thermistor causes a trip event, and the
inverter turns OFF the motor
Description
Starts the motor rotation
No change to present motor status
Stops the motor rotation
No change to present motor status
Selects the direction of motor rotation: ON = FWD. While the
motor is rotating, a change of F/R will start a deceleration,
followed by a change in direction
2nd-stage
acceleration
standard
acceleration

and
and