Table 1.32 Buttons In The [System Setup] Window - Fujitsu PRIMEQUEST 1000 Series Tool Reference

Hide thumbs Also See for PRIMEQUEST 1000 Series:
Table of Contents

Advertisement

PRIMEQUEST 1000 Series Tool Reference
CHAPTER 1 MMB Web-UI (Web User Interface) Operations
Item
Shutdown Delay after
Sets the standby time as the period from when the UPC interface detects a power failure
UPS detects AC
to when the partition power-off sequence starts. If the power is restored within this period,
Failure
the partition is not powered off. You can specify a value in a range of 0 to 9999.
The default is 5 seconds.
Partition Power On
Sets the standby time as the period until the partition power-on sequence is indicated
Delay
according to the set power restoration policy. The policy is specified when the UPC
interface detects power restoration or after AC power-on (including the power restoration
time). You can specify a value in a range of 0 to 9999.
The default is 0 seconds.
Altitude
Sets the altitude at which the PRIMEQUEST 1000 series system is installed.
The default is Altitude <= 500 m.
The altitude specifications include an allowable margin of error of +/-100 m.
PSU Redundant Mode Sets whether to apply redundant operation for the PSU.
If [Power Feed Mode] is Single, the default is Non-redundant.
If [Power Feed Mode] is Dual, Redundant is the fixed value.
Reserved SB Force
Sets the maximum standby time before the forced power-off sequence starts for the
Power Off Wait
partition containing the relevant SB, for switching to a Reserved SB. You can specify a
value in a range of 0 to 99.
The default is 10 minutes.

TABLE 1.32 Buttons in the [System Setup] window

Button
Apply
Click the [Apply] button to set the specified information, such as [Power Feed Mode] and
[Power Restore Policy].
Cancel
Click the [Cancel] button to restore the original information and not set the changed or
entered information.
(1) Menu operations
[System] - [System Setup]
(2) Window operations
1. Specify items such as [Power Feed Mode] or [Power Restoration Policy]. Then, click the [Apply] button.
This sets the information for each item.
Messages
- Altitude <= 500 m
- 500 m < Altitude <= 1000 m
- 1000 m < Altitude <= 1500 m
- 1500 m < Altitude
- Redundant
- Non-redundant
Description
Description
78
C122-E110-10EN