Operation On Error - Mitsubishi Electric M800VW Series Manual

Plc development
Hide thumbs Also See for M800VW Series:
Table of Contents

Advertisement

M800V/M80V Series PLC Development Manual
5 Peripheral Development Environment (GX Works2)
5.5 Common Items

5.5.11.5 Operation on Error

An error is generated under the following condition, and an error dialog is displayed on the GX Works2 screen when
parameters are checked on trace execution.
No.
Device setting has no devices that are traceable
(1)
Trace setting has invalid conditions.
(2)
Detailed trace setting has no valid devices set.
(3)
The capacity of trace data exceeds the capacity per project
(4)
When trace cannot be executed, check the following.
 Ensure that the CPU type is "Q26UCPU"
 Check the trace execution status (Trace execution cannot be commanded during trace.)
 When "Execute using existing trace settings in the PLC" is selected in the trace execution setting, check whether the set-
ting file is saved in the CNC
 Check the consistency between the devices on the program and devices in the trace setting
IB-1501614-B
Error details
Remedies
Set a traceable device for "Sampling Trace" screen.
Set valid conditions for trace set.
Set a valid device in detailed trace setting.
Set the capacity of trace data that does not exceed the capacity
per project.
114

Advertisement

Table of Contents
loading

This manual is also suitable for:

M800vs seriesM80vw seriesM80v seriesM850vwM830vwM850vs ... Show all

Table of Contents