Checklists for AC500-S commissioning
Verification procedure for safe iParameter setting in AC500-S safety I/Os > Verification tables for iParameter settings in AC500-S safety I/Os
5.
6.
Important!
If any errors (F_iPar_CRC or iParameters are not equal) were identified during Steps 1 ... 6,
then one has to re-do the same procedure from the beginning. If after this second repetition
there is still inconsistency, contact ABB technical support for help.
Note, if iParameters values were verified as described in Steps 1 ... 6, you can re-use this
iParameter combination with the given F_iPar_CRC for further modules of the same type
without repeating the verification procedure described above.

6.5.2 Verification tables for iParameter settings in AC500-S safety I/Os

The instructions below provide a basis for cross-check of values set for iParameters in "AI581-
S" , "DI581-S" and "DX581-S" tabs.
334
Go to "<safety I/O module name> Parameters" tab, and verify using a cross-check
Ä Chapter 6.5.2 " Verification tables for iParameter settings in AC500-S
according to
safety I/Os" on page 334 that iParameter settings previously set at Step 2 are the same as
ones listed in the "Value" column for given channels (use
tables for iParameter settings in AC500-S safety I/Os" on page 334 to decode integer
values to real parameter values).
Go to "F-Parameter" tab and press [Calculate] button once more, even if the previous
value is still available. Compare that the value shown in "Checksum iParameter" field and
the one in F_iPar_CRC field of the F-Parameter editor are the same.
ð If F_iPar_CRC values are the same, then the verification procedure for given iPara-
meter settings of the given AC500-S safety I/O module was successfully passed.