Checklist For Operation, Maintenance And Repair - ABB AC500-S Safety User Manual

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Checklists for AC500-S commissioning

Checklist for operation, maintenance and repair

No.
Item to check
11.
Verify that the following rules were correctly applied for
safe CPU to CPU communication using SM560-S-FD-1
and SM560-S-FD-4 CPUs:
In the same codename space, F_Dest_Add shall be
unique (Fig. 6 on page 38).
In the same codename space, F_Source_Add shall
not be re-used in other F-Hosts. Inside the same F-
Host, a re-use is allowed for several F-Host Drivers.
In the same codename space, F_Dest_Add shall not
be used as F_Source_Add and vice versa.
12.
If SM560-S-FD-1 or SM560-S-FD-4 is used, make sure
that safety communication modules ("12 Byte In/Out
(Safety)" / "8 Byte and 2 Int In/Out (Safety)" are correctly
connected to master systems.
13.
Verify that not only codenames but also F_Dest_Add are
unique in PROFIsafe networks, if only F_Dest_Add is
checked by the F-Device.
Reviewer(s):
Machine/Application <ID>:
Signature:
Date:
6.4 Checklist for operation, maintenance and repair
No.
Item to check
1.
Make sure that all safety modules are properly placed on
their positions at the terminal base for safety CPU or ter-
minal units for safety I/Os and stable contact between
terminals and safety modules is assured.
2
Check that proper temperature monitoring measures
(e.g., temperature sensors could be placed in the control
cabinet and connected to AI581-S safety analog input
channels) are implemented in the control cabinet where
AC500-S safety modules are placed, if the operating tem-
perature range for AC500-S safety PLC cannot be guar-
anteed.
Note:
Safety digital outputs of DX581-S module have internal
built-in overtemperature protection and always deliver
fail-safe "0" values in case of overtemperature.
330
Fulfilled (yes / no)?
Fulfilled (yes / no)?
3ADR025091M0208, 12, en_US
Comment
Comment
2020/06/19