Checklists for AC500-S commissioning
Verification procedure for safe iParameter setting in AC500-S safety I/Os > Verification tables for iParameter settings in AC500-S safety I/Os
4.
Fig. 123: Compare "DI581-S" tab and "DI581-S Parameters" tab
1
"2 channel configuration 0/8" parameter in "DI581-
S" tab
2
"Inputs 0/8, discrepancy time" parameter in "DI581-
S Parameters" tab
5.
338
Compare that "2 channel configuration 0/8" parameter in "DI581-S" tab have the same
value as "Inputs 0/8, discrepancy time" parameter in "DI581-S Parameters" tab.
The values have to be the same.
If they are not the same, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verifica-
tion procedure and contact ABB technical support.
Repeat step 4 for the rest of channel combinations:
Inputs 1/9, discrepancy time
Inputs 2/10, discrepancy time
Inputs 3/11, discrepancy time
Inputs 4/12, discrepancy time
Inputs 5/13, discrepancy time
Inputs 6/14, discrepancy time
Inputs 7/15, discrepancy time
3ADR025091M0208, 12, en_US