Usage of safety CPU with V2 non-safety CPU PM5xx
B.2.1
Error messages for safety CPUs
The errors are shown as they are displayed in Automation Builder.
Table 104: Common error messages for SM560-S / SM560-S-FD-1 / SM560-S-FD-4 safety CPUs
Error
Compo-
Device
severity
nent or
interface
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
368
Module
Channel
Error
30
1
0
30
1
1
30
1
2
30
1
12
30
1
18
30
1
28
30
1
40
30
1
43
30
1
48
30
1
52
30
2
0
30
2
1
30
2
2
30
2
3
3ADR025091M0208, 12, en_US
Error text
Remedy
Operation fin-
Change safety PLC switch
ished.
address setting or remove
SD-card from non-safety
PLC.
Restart safety PLC. If this
error persists, replace safety
PLC.
Wrong user
Delete user data from safety
data
PLC. Restart safety PLC and
write user data again.
Internal
Restart safety PLC. If this
PROFIsafe initi-
error persists, replace safety
alization error
PLC. Contact ABB technical
support.
Flash read error Restart safety PLC. If this
error persists, replace safety
PLC. Contact ABB technical
support.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Boot project
Reload boot project. If this
download error
error persists, replace safety
PLC.
Wrong firmware
Update safety PLC firmware.
version
Restart safety PLC. If this
error persists, replace safety
PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Overvoltage or
Restart safety PLC. Check
undervoltage
safety PLC setting for power
detected
supply error. If this error per-
sists, replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
User program
Check user program
triggered safe
stop
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal
Restart safety PLC. If this
PROFIsafe error
error persists, replace safety
PLC. Contact ABB technical
support.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.