DiagCode
8030
8000
8012
8013
2020/06/19
State name
State description and output setting
Test Active
The automatic sensor test is active. Test Timer is started second
time.
The transmitter signal of the sensor is switched on by the FB.
The signal of the receiver must follow the signal of the transmitter.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
ESPE Free
The FB has not detected a safety demand.
Test ok
The sensor was automatically tested.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = TRUE
TestExecuted = TRUE
Error = FALSE
ESPE Inter-
The FB has detected a safety demand.
rupted 2
The switch was automatically tested.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = FALSE
Wait for
Wait for rising trigger of Reset after state 8012.
Reset 2
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = FALSE
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib