C.2
Error messages with AC500 V3 non-safety CPUs
C.2.1
Error messages for safety CPUs
The errors are shown as they are displayed in Automation Builder. In CODESYS Safety, errors
are displayed similar to error messages of V2 non-safety CPUs.
Table 113: Error messages for safety CPU
Severity
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2020/06/19
Error code
Description
8235
Internal error
8448
Operation finished
8449
Wrong user data
8450
Internal PROFIsafe initiali-
zation error
8460
Flash read error
8466
Internal error
8476
Boot project download
error
8488
Wrong firmware version
8491
Internal error
8496
Overvoltage or under-
voltage detected
8500
Internal error
8704
User program triggered
safe stop
8705
Internal error
8706
Internal PROFIsafe error
8707
Internal error
8714
Internal error
8717
Flash write error
3ADR025091M0208, 12, en_US
Usage of safety CPU with V3 non-safety CPU PM56xx
Remedy
Replace module
Change Safety PLC switch
address setting or remove SD-
Card from non-safety PLC.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Delete user data from Safety
PLC. Restart Safety PLC and
write user data again.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Contact ABB technical support.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Contact ABB technical support.
Contact ABB technical support.
Replace Safety PLC.
Reload boot project. If this error
persists, replace Safety PLC.
Update Safety PLC firmware.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Contact ABB technical support.
Replace Safety PLC.
Restart Safety PLC. Check
Safety PLC setting for power
supply error. If this error per-
sists, replace Safety PLC.
Contact ABB technical support.
Replace Safety PLC.
Check user program
Contact ABB technical support.
Replace Safety PLC.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Contact ABB technical support.
Contact ABB technical support.
Replace Safety PLC.
Contact ABB technical support.
Replace Safety PLC.
Restart Safety PLC. If this error
persists, replace Safety PLC.
Contact ABB technical support.
385