Do these manual checks for each safety device in the SVT checklist. You can skip the sections
for safety devices only if the data checksum for the safety device is identical to the previously
validated and approved SVT checklist.
How to verify
In the libraries section (Fig. 83 on page 165), verify that the library CRCs correspond to the
the libraries
AC500-S libraries
section
How to verify
Verify that the SVT checklist ends with the line "End of SVT checklist" , and if so, mark the cor-
the end of the
responding checkbox in the project information section (Fig. 84 on page 165).
SVT checklist
Errors in the
If there are errors in the automatic consistency checks, SVT shows this with an error message
automatic
in the project information section of the SVT checklist.
checks
2020/06/19
System configuration and programming > Checking of program and system configuration
Verify the I/O mapping information for the safety device.
Note that "Data type" and "I/O" are listed for information only.
Verify F-Parameter values for the safety device.
Ä Chapter 4.6 "AC500-S libraries" on page 182.
3ADR025091M0208, 12, en_US
Configuration and programming
169