Self-test and
Start-up and runtime tests: Program flow control, RAM, CPU, ADC, etc.
diagnostic func-
tions
Dimensions,
Data
weight
W x H x D
Weight (without terminal unit)
Certifications
CE, cUL (further certifications at www.abb.com/plc)
3.5.9.1
Technical data of safety analog inputs
Data
Number of channels per module
Configurability, 1 channel mode
Configurability, 1 channel mode
Configurability, 2 channel mode
Channel input resistance, in active mode
Channel input resistance, in inactive mode
Distribution of
2 groups of 2 channels each.
channels into
groups
Data
Time constant of the input filter
Conversion cycle
Resolution
Temperature coefficient ± % of full scale (0 ... 20 mA)
Maximum error at +25 °C ± % of full scale (0 ... 20 mA)
Maximum error over full temperature range ± % of full
scale (0 ... 20 mA)
Value of a LSB (least significant bit)
Maximum permanent allowed overload (no damage)
(self-protected), voltage
Maximum permanent allowed overload (no damage)
(self-protected), current
Non-linearity (of full scale)
Sample repetition time
Input filter characteristics - first order, filter time constant
Transition frequency
2020/06/19
DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or >
+35 V DC) could lead to unrecoverable damage of the system.
3ADR025091M0208, 12, en_US
AC500-S safety modules
AI581-S safety analog input module > Technical data
Value Unit
67.5 x 76 x 62 mm
~ 130 g
Value Unit
0 ... 20 mA
4 ... 20 mA
4 ... 20 mA
~ 125 Ω
~ 15 kΩ
Value Unit
0.33 ms
14 bits
±0.005 %/K
± 0.25 %
± 0.25 %
2.03 µA
32 V DC
24 mA
±0.05 %
3.3 ms
160 Hz
4
1 ms
1 ms
121