Verification procedure for safe iParameter setting in AC500-S safety I/Os > Verification tables for iParameter settings in AC500-S safety I/Os
2.
3.
2020/06/19
Refer to "DI581-S" tab and calculate "Input channel 0" decimal equivalent
(Dec_InputChannel0) as:
Dec_InputChannel0 = Configuration_Value + Test_Pulse_Value + Input_Delay_Value
where
Configuration_Value:
0 ➔ Not used
1 ➔ 1 channel
2 ➔ 2 channel equivalent
3 ➔ 2 channel antivalent
Test_Pulse_Value:
0 ➔ Disabled
8 ➔ Enabled
Input_Delay_Value:
16 ➔ 1 ms
32 ➔ 2 ms
48 ➔ 5 ms
64 ➔ 10 ms
80 ➔ 15 ms
96 ➔ 30 ms
112 ➔ 50 ms
128 ➔ 100 ms
144 ➔ 200 ms
160 ➔ 500 ms
Compare calculated Dec_InputChannel0 with "Input 0, channel configuration value".
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verifica-
tion procedure and contact ABB technical support.
Repeat step 2 for the rest of digital input channels (input 1, input 2, ... input 15).
3ADR025091M0208, 12, en_US
Checklists for AC500-S commissioning
337