ABB AC500-S Safety User Manual page 57

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

3.2.2.2
Transitions between safety I/O module states
Transition
From
(Fig. 14 on
page 51, Fig. 15
on page 51)
(1)
INIT
(2)
RUN (ok)
(3)
INIT
(4)
RUN (module pas-
sivation)
(5)
INIT
(6)
SAFE STOP
(7)
RUN (ok)
(8)
RUN (channel
passivation and
reintegration)
(9)
RUN (ok)
(10)
RUN (ok)
(11)
RUN (ok)
(12)
RUN (channel
passivation and
reintegration)
(13)
RUN (module pas-
sivation)
(14)
RUN (channel
passivation and
reintegration)
(15)
INIT
(16)
RUN (user
acknowledgment
request)
2020/06/19
To
Description
RUN (ok)
Safety I/O module comes to this state directly after
INIT during a normal start-up
INIT
Powering off/on
RUN (module pas-
PROFIsafe watchdog, PROFIsafe communication
sivation)
error or undervoltage/overvoltage was detected
directly after INIT.
The safety I/O module can reach this state also after
powering off/on the safety I/O module if safety CPU
with PROFIsafe F-Host continues running and brings
safety I/O module to a fail-safe RUN (module passi-
vation) state after powering off/on
INIT
Powering off/on
SAFE STOP
Error(s) of severity level 1 (CPU test, RAM test, etc.
failed) took place
INIT
Powering off/on
RUN (channel
Channel error was identified by the safety I/O
passivation and
module. The tests (whenever it is possible) are con-
reintegration)
tinued for the given channel to be able to see if the
error is gone (e.g., wiring error was corrected). As
soon as the error is gone, the module sets "Reinte-
gration request" bit = "1" for the given channel.
RUN (ok)
SAFE STOP
Error(s) of severity level 1 (CPU test, RAM test, etc.
failed) took place
RUN (module pas-
PROFIsafe watchdog, PROFIsafe communication
sivation)
error or undervoltage/overvoltage was detected.
RUN (module pas-
"activate_FV_C = 1" command was sent from the
sivation with a
safety CPU
command)
SAFE STOP
Error(s) of severity level 1 (CPU test, RAM test, etc.
failed) took place
SAFE STOP
Error(s) of severity level 1 (CPU test, RAM test, etc.
failed) took place
INIT
Powering off/on
INIT
Powering off/on
SAFE STOP
Error(s) of severity level 1 (CPU test, RAM test, etc.
failed) took place
3ADR025091M0208, 12, en_US
Generic safety I/O module behavior > Safety I/O module states
The channel error is gone.
"Reintegration request" bit = 1 is set for the given
channel by the safety I/O module.
"Acknowledge reintegration" bit (positive edge) is
set by PROFIsafe F-Host for the given channel
AC500-S safety modules
57