Function block-
Table 25: FB-specific error codes
specific error
DiagCode
and status
codes
C001
C002
C003
Table 26: FB-specific status codes (no error):
DiagCode
0000
8001
8000
8004
2020/06/19
State name
State description and output setting
Error 1
Discrepancy time elapsed in state 8004.
Ready = TRUE
S_AntivalentOut = FALSE
Error = TRUE
Error 2
Discrepancy time elapsed in state 8014.
Ready = TRUE
S_AntivalentOut = FALSE
Error = TRUE
Error 3
Discrepancy time elapsed in state 8005.
Ready = TRUE
S_AntivalentOut = FALSE
Error = TRUE
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_AntivalentOut = FALSE
Error = FALSE
Init
An activation has been detected by the FB and the FB is now
activated.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE
Safety
The inputs switched to the Active state in antivalent mode.
Output Ena-
Ready = TRUE
bled
S_AntivalentOut = TRUE
Error = FALSE
Wait for NO
ChannelNC has been switched to TRUE - waiting for ChannelNO
to be switched to FALSE; discrepancy timer started.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE