Validity; Important User Information - ABB AC500-S Safety User Manual

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Rev.
Description of version / changes
1.0.1
Minor typos were corrected. TÜV SÜD certificate was added.
The text was changed in the document:
Safety I/O inputs and outputs are not electrically isolated from the
other electronic circuitry of the module.
The safety values for safety outputs of DX581-S (-XC) module are
only valid if the parameter "Detection" is set to "On".
DC (diagnostic coverage) for DX581-S (-XC) module shall be
≥ 94 %.
The clarification was added that the boot project update on SM560-S
is possible only if no boot project is loaded on SM560-S.
Not more than one communication error (CE_CRC or Host_CE_CRC
output signals become equal to TRUE) per 100 hours is allowed to
be acknowledged by the operator using OA_C input signal without
consulting the responsible safety personnel.
SM560-S cycle time shall be included three times instead of two
times in Safety Function Response Time calculation.
The values for input delay accuracy in Safety Function Response
Time calculation were updated.
Update of Appendix A with system data for AC500-S-XC.
1.0.0
First release

1.3 Validity

The data and illustrations found in this documentation are not binding. ABB reserves the right to
modify its products in line with its policy of continuous product development.

1.4 Important user information

This documentation is intended for qualified personnel familiar with functional safety. You must
read and understand the safety concepts and requirements presented in this safety user
manual prior to operating AC500-S safety PLC system.
The following special notices may appear throughout this documentation to warn of potential
hazards or to call attention to specific information.
2020/06/19
DANGER!
The notices referring to your personal safety are highlighted in the manual by
this safety alert symbol, which indicates that death or severe personal injury
may result if proper precautions are not taken.
NOTICE!
This symbol of importance identifies information that is critical for successful
application and understanding of the product. It indicates that an unintended
result can occur if the corresponding information is not taken into account.
3ADR025091M0208, 12, en_US
Introduction
Important user information
Who
Date
ABB
08.03.2013
ABB
19.12.2012
7

Advertisement

Table of Contents
loading