ABB AC500-S Safety User Manual page 105

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Data
Number of channels per module (transistor outputs)
Terminals of reference potential for all outputs (minus
pole of the process supply voltage, signal name ZP)
Terminals of common power supply voltage for all out-
puts (plus pole of the process supply voltage, signal
name UP)
Output voltage for signal 1
Output delay (0 ➔ 1 or 1 ➔ 0): 5 mA output current
Output delay (0 ➔ 1 or 1 ➔ 0): 500 mA output current
Ability to switch a capacitive load of at least
Ability to switch an inductive load of at least
Output current
Data
Rated value, per channel at UP = 24 V
Maximum value (all channels together)
Leakage current with signal 0
Short-circuit proof/overload proof
Overload message (channel passivation), I > 0.7 A
Output current limitation (automatic reactivation after
short-circuit/overload)
Resistance to feedback against 24 V signals
Demagnetization by internal suppressor diodes when
switching off inductive loads
Rated protection fuse on UP
Cable length
Data
Max. cable length, shielded
Max. cable length, unshielded
3.4.9.3
Technical data of non-safety test pulse outputs
Data
Number of test pulse channels per module (transistor
test pulse outputs)
Terminals of the channels T0, T1
Terminals of the channels T2, T3
Terminals of reference potential for all test pulse outputs
(minus pole of the process supply voltage, signal name
ZP)
Terminals of common power supply voltage for all out-
puts (plus pole of the process supply voltage, signal
name UP)
Output voltage for signal 1
2020/06/19
DX581-S safety digital input/output module > Technical data
3ADR025091M0208, 12, en_US
AC500-S safety modules
Value Unit
8
1.9 ... 4.9
1.8 ... 4.8
UP - 3 V
1 ms
4 ms
300 µF
1 H
Value Unit
500 mA
4 A
< 0.5 mA
yes
yes
yes
yes
yes
4.5 A
Value Unit
1000 m
600 m
Value Unit
4
1.0, 1.2
3.0, 3.2
1.9 ... 4.9
1.8 ... 4.8
UP - 0.8 V
105

Advertisement

Table of Contents
loading

Table of Contents