System configuration and programming > Instantiation and configuration of safety modules / definition of variable names
F_Parameter
Definition
F_Source_Add
F-Host source address. The
F_Source_Add parameter is a log-
ical address designation that can
be assigned freely but unambigu-
ously.
F_Source_Add shall not be
equal to F_Dest_Add for the
given F-Device.
F_Dest_Add
The unique F-Device address
which will be compared with the
set hardware switch address in F-
Device. The F_Dest_Add param-
eter is a logic address designation
that can be assigned freely but
unambiguously.
F_WD_Time
Watchdog time in ms for receipt of
the new valid telegram
F_iPar_CRC
CRC over iParameters (manufac-
turer-specific) of F-Devices (safety
I/Os).
F_Par_CRC
CRC1 signature calculation across
the F-Parameters
iParameters are individual F-Device parameters which are transferred to F-Devices with a
proper F_iPar_CRC parameter.
2020/06/19
NOTICE!
AC500-S PROFIsafe F-Host implementation does not support or only partially
supports the following PROFIsafe conformance class
Communication function block set RDREC, WRREC, RDIAG and RALRM,
Ä [12]
as defined in
iPar server services
Data types: Unsigned32, Integer32 and real data types like Float32, etc.
Tool calling interface, as defined in
3ADR025091M0208, 12, en_US
Allowed values
[1 - 511] for SM560-S-FD-1
and SM560-S-FD-4
[1 - 239] for AC500-S
safety I/O modules
[1 - 65534] for 3
rd
party
PROFIsafe F-Devices (if
no limitations of
F_Source_Add are defined
by the manufacturer)
0 and 65535 is not
allowed.
[1 - 255] for AC500-S
safety I/O modules.
For SM560-S-FD-1 and
SM560-S-FD-4:
F_Dest_Add = Address
Switch Value (1 - 239) *
100 + F-Device
instance no. (0..31)
Addresses switch
values [240 - 255] are
reserved for system
functions.
[10 - 10000]
[0 - 4294967295]
Hex [0 - FFFFFFFF]
[0 - 65535]
Hex [0 - FFFF]
Ä [3].
Configuration and programming
Default value
1
2 for safety I/O modules
100 for SM560-S-FD-1 or
SM560-S-FD-4
ABB F-Devices: 100
3
rd
party F-Devices:
according to GSDML file
Dependent on the module
type
Dependent on the module
type
Ä [3] functions:
137