Circuit Examples - ABB AC500-S Safety User Manual

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

AC500-S safety modules
AI581-S safety analog input module > Circuit examples
No.
Name
1
Check supply
2
Configuration
3
Noise rejection
4
Tolerance range (used
only for "2 channel
(4 ... 20 mA)" mode)
5
Used value (min/max)
(used only for "2
channel (4 ... 20 mA)"
mode)

3.5.7 Circuit examples

Examples of electrical connections and reachable SIL (IEC 61508), SILCL (IEC 62061) and PL
(ISO 13849-1) with AI581-S module are presented below.
114
Values
"On", "Off"
"Not used", "1 channel (0 ... 20 mA)", "1 channel
(4 ... 20 mA)", "2 channel (4 ... 20 mA)"
"50 Hz", "60 Hz", "None"
"4 %", "5 %", "6 %", "7 %", "8 %", "9 %", "10 %",
"11 %", "12 %"
"Minimum", "Maximum"
NOTICE!
Whenever DC = High is used in the circuit examples with safety analog inputs,
the following measure from ISO 13849-1
Cross monitoring of input signals and intermediate results within the logic (L),
and temporal and logical software monitor of the program flow and detection of
static faults and short circuits (for multiple I/O).
Whenever DC = Medium is used in the circuit examples with safety analog
inputs, any of the measures for input devices with DC ³ 90 % can be used from
ISO 13849-1
Ä [10].
3ADR025091M0208, 12, en_US
Default
"On"
"Not used"
"50 Hz"
"4 %"
"Minimum"
Ä [10] is used with AI581-S module: