ABB AC500-S Safety User Manual page 94

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

AC500-S safety modules
DX581-S safety digital input/output module > Mounting, dimensions and electrical connection
The terminals 1.8, 2.8, 3.8 and 4.8 as well as 1.9, 2.9, 3.9 and 4.9 are electrically intercon-
nected within the I/O terminal unit and have always the same assignment, independent of the
inserted module:
Terminals 1.8, 2.8, 3.8 and 4.8: Process voltage UP = +24 V DC
Terminals 1.9, 2.9, 3.9 and 4.9: Process voltage ZP = 0 V
The assignment of the other terminals:
Terminals
1.0, 1.2, 3.0, 3.2
2.0 ... 2.3, 4.0 ... 4.3
2.4 ... 2.7, 4.4 ... 4.7
1.8, 2.8, 3.8, 4.8
1.9, 2.9, 3.9, 4.9
1.1, 1.3, 1.4, 1.5, 1.6, 1.7, 3.1, 3.3,
3.4, 3.5, 3.6, 3.7
Examples of
Examples of electrical connections with DX581-S module, single channels Ix and Ox.
connections
Fig. 43: Example of electrical connections with DX581-S
94
Signal
T0, T1, T2, T3
I0, I1, I2, I3, I4, I5, I6, I7
O0, O1, O2, O3, O4, O5, O6, O7
UP
ZP
Free
NOTICE!
The process voltage must be included in the earthing concept of the control
system (e.g., earthing the minus pole).
I0
2.0
I1
2.1
I2
2.2
I3
2.3
I4
4.0
I5
4.1
I6
4.2
I7
4.3
1.8
UP +24 V
ZP 0 V
1.9
3ADR025091M0208, 12, en_US
Meaning
Connectors of 4 test pulse outputs
T0, T1, T2, T3
8 safety digital inputs
8 safety digital outputs
Process power supply +24 V DC
Central process earth
Not used
2.4 O0
2.5 O1
2.6 O2
2.7 O3
4.4 O4
4.5 O5
4.6 O6
4.7 O7
2.8
2.9
U
out
T0 1.0
U
out
T1 1.2
U
out
T2 3.0
U
out
T3 3.2
3.8
4.8
3.9
4.9
2020/06/19

Advertisement

Table of Contents
loading

Table of Contents