Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
C005
C006
Table 53: FB-specific status codes (no error):
DiagCode
0000
8000
8001
8002
8003
250
State name
State description and output setting
Parameter
MaxMutingTime value out of range.
Error
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error Timer
Timing error: Active muting time (when S_MutingActive = TRUE)
MaxMuting
exceeds MaxMutingTime.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
AOPD Free
Muting not active and no safety demand from AOPD.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Init
Function block has been activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Safety
Safety demand detected by AOPD, muting not active.
Demand
Ready = TRUE
AOPD
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Wait for
Safety demand or errors have been detected and are now
Reset
cleared. Operator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US