Table 50: FB-specific status codes (no error):
DiagCode
0000
8001
8002
8003
8004
2020/06/19
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
Init
An activation has been detected by the FB.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
ESPE Inter-
The FB has detected a safety demand.
rupted 1
The switch has not been automatically tested yet.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
Wait for
Wait for rising trigger of Reset after state 8002.
Reset 1
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
External
The automatic sensor test was faulty.
Function
An external manual sensor test is necessary.
Test
The support for the necessary external manual sensor test has
been activated at the FB (NoExternalTest = FALSE).
A negative signal edge at the sensor is required.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
241